  1.                          SECTION 16132
  2.  
  3.                   SURFACE NONMETALLIC RACEWAYS
  4. NOTE ** The Wiremold Company Access 5000, 5400, and 5500
  5.         surface non-metallic raceway systems.
  6. NOTE **
  7. NOTE ** This section is based on the Access 5000, 5400, and
  8.         5500 surface non-metallic raceway systems
  9.         manufactured by The Wiremold Company, at the
  10.         following address:
  11. NOTE **     60 Woodlawn Street
  12. NOTE **     West Hartford CT 06133-2500
  13. NOTE **     Tel:  (800) 621-0049
  14. NOTE **     Fax:  (203) 232-2062
  15. NOTE **
  16. NOTE ** The Wiremold Company offers a complete line of
  17.         products for communications, data, and electrical
  18.         wiring management.
  19. NOTE **
  20. NOTE ** SECTION 16132 - SURFACE NONMETALLIC RACEWAYS,
  21.         Copyright 1998, The Architect's Catalog, Inc.
  22.  
  23.  
  24. PART 1  GENERAL
  25.  
  26. 1.1 SECTION INCLUDES
  27. NOTE ** Delete items below not required for project.
  28.  
  29.     A.  Surface Non-Metallic Raceways.
  30.  
  31.     B.  Fittings.
  32.  
  33.     C.  Device Brackets and Plates.
  34.  
  35.     D.  Cover Brackets and Face Plates.
  36.  
  37.     E.  Communications Devices and Accessories.
  38.  
  39.     F.  Electrical Devices.
  40.  
  41. 1.2 RELATED SECTIONS
  42. NOTE ** Add any sections below relevant to this project.
  43.  
  44.     A.  Sections of Division 16 affected by, or affecting,
  45.         construction activities of this section.
  46.  
  47. 1.3 REFERENCES
  48.  
  49.     A.  National Electrical Code.
  50.  
  51.     B.  UL 94 - Tests for Flammability of Plastic Materials for
  52.         Parts in Devices and Appliances; Underwriter's
  53.         Laboratories, Inc.
  54.  
  55. 1.4 SYSTEM DESCRIPTION
  56.  
  57.     A.  Performance Requirements:
  58.         1.  Surface non-metallic raceway for dry interior
  59.             locations, conforming to National Electrical Code,
  60.             Article 352, Part B.
  61.         2.  System components listed by Underwriter's
  62.             Laboratories, Inc.,  exhibiting non-flammable,
  63.             self-extinguishing characteristics when tested in
  64.             accordance with UL 94, V-O.
  65.  
  66. 1.5 SUBMITTALS
  67.  
  68.     A.  Submit under provisions of Section 01300.
  69.  
  70.     B.  Product Data:  Manufacturer's descriptive literature for
  71.         each system component specified in this section.
  72.  
  73.     C.  Shop Drawings:  Indicate raceway layouts, each system
  74.         component required for complete system, raceway lengths,
  75.         device types, locations; identify all circuits.
  76.  
  77.     D.  Quality Assurance Submittals:
  78.         1.  Test Reports:  Certified reports from independent
  79.             testing laboratory supporting compliance of raceway
  80.             system to specified requirements.
  81.         2.  Manufacturer's instructions:  Printed installation
  82.             instructions for each system component; include
  83.             storage requirements.
  84.  
  85.     E.  Closeout Submittals:  If variations from approved shop
  86.         drawings occur during installation of raceway system,
  87.         submit final as-built drawings indicating such
  88.         variations.
  89.  
  90. 1.6 DELIVERY, STORAGE, AND HANDLING
  91.  
  92.     A.  Store products of this section in manufacturer's unopened
  93.         packaging until installation.
  94.  
  95.     B.  Maintain storage area conditions for products of this
  96.         section in accordance with manufacturer's instructions
  97.         until installation.
  98.  
  99.  
  100. PART 2  PRODUCTS
  101.  
  102. 2.1 MANUFACTURERS
  103.  
  104.     A.  Acceptable Manufacturer:  The Wiremold Company; 60
  105.         Woodlawn Street, West Hartford CT 06133-2500; ASD. Tel:
  106.         (800) 621-0049, Fax: (203) 232-2062.
  107. NOTE ** Delete one of the two following paragraphs;
  108.         coordinate with Division 1 requirements.
  109.  
  110.     B.  Requests for substitutions will be considered in
  111.         accordance with provisions of Section 01600.
  112.  
  113.     C.  Substitutions:  Not permitted.
  114. NOTE ** Delete following paragraph if substitutions not
  115.         permitted.
  116.  
  117.     D.  Supply all products specified in this section from a
  118.         single manufacturer.
  119.  
  120. 2.2 COMPONENTS
  121. NOTE ** Retain the following paragraphs if specifying
  122.         Wiremold Access 5000 System.
  123.  
  124.     A.  Surface Non-Metallic Raceway:
  125.         1.  Acceptable Product:  Wiremold Access 5000 System.
  126.         2.  Product Description:  Three-piece system of rigid
  127.             polyvinyl chloride (PVC) extrusions, 8 feet (2438 mm)
  128.             in length with nominal 0.09 inch (2.38 mm) wall
  129.             thickness, total 5.78 inches (146.8 mm) high by 0.96
  130.             inches (24.4 mm) deep, consisting of the following:
  131.             a.  Base:  Smooth finish, neutral color extruded
  132.                 channel, with integral continuous barrier
  133.                 separating channel interior into two wiring
  134.                 channels, and with continuous integral ribs in
  135.                 top channel to receive mounting device brackets.
  136.             b.  Cover:  Extruded flat profile, with continuous
  137.                 integral flanges at each edge for snap on fit to
  138.                 open face of base; sight-exposed surface of cover
  139.                 finished to match trim cover.
  140. NOTE ** Insert finish requirements in the following
  141.         paragraph; a full selection of finishes is
  142.         available, including but not limited to, matte
  143.         texture, white color, gray and black vinyl,
  144.         laminates, maple, mahogany, cherry and oak wood
  145.         veneers.
  146.             c.  Trim cover:  Extruded cove profile, with
  147.                 continuous integral flanges at each edge for snap
  148.                 on fit to top of base; sight-exposed surface of
  149.                 trim cover finished and coordinated with cover.
  150.  
  151.     B.  Corner Units:
  152.         1.  Supply factory-formed cover and trim cover units for
  153.             internal and external corners of indicated raceway
  154.             layouts:
  155.             a.  External corner units:  Minimum 2-1/2 inch (63.5
  156.                 mm) leg length.
  157.             b.  Internal corner units:  Minimum 1-5/8 inch (31.7
  158.                 mm) leg length.
  159.         2.  Finish corner units to compliment linear cover and
  160.             trim cover units.
  161.  
  162.     C.  Fittings:
  163.         1.  Supply factory-formed fittings specified in
  164.             manufacturer's product data for indicated
  165.             configurations and service requirements, and as
  166.             follows:
  167. NOTE ** Retain one of the following two paragraphs.
  168.             a.  Base coupling and cover clip for each vertical
  169.                 joint between cover unit sections, including
  170.                 corner units.
  171.             b.  Base coupling and internal wire guard for each
  172.                 vertical joint between cover unit sections,
  173.                 including corner units.
  174. NOTE ** Retain the following paragraph; edit if project
  175.         requirements differ.
  176.             c.  One wire clip of each size for every 2 linear
  177.                 feet (609 mm) of indicated base configuration.
  178. NOTE ** Retain one of the following two paragraphs.
  179.         2.  Finish:  White.
  180.         3.  Finish:  Brown.
  181. NOTE ** Retain the following paragraphs if specifying
  182.         Wiremold 5400 System.
  183.  
  184.     D.  Surface Non-Metallic Raceway:
  185.         1.  Acceptable Product:  Wiremold 5400 System.
  186.         2.  Product Description: Two-piece system of rigid
  187.             polyvinyl chloride (PVC) extrusions, 8 feet (2438 mm)
  188.             in length with nominal 0.10 inch (2.5 mm) wall
  189.             thickness, total 5-1/2 inches (139.7 mm) high by 1-
  190.             3/4 inches (44.4 mm) deep, consisting of the
  191.             following:
  192. NOTE ** Retain the following paragraph if specifying
  193.         Wiremold 5400B base.
  194.             a.  Base:  Smooth finish, ivory or white color
  195.                 extruded channel, with integral continuous
  196.                 barrier separating channel interior into two
  197.                 wiring channels of equal width.
  198. NOTE ** Retain the following paragraph if specifying
  199.         Wiremold 5400D base.
  200.             b.  Base:  Smooth finish, ivory or white color
  201.                 extruded channel, with integral continuous
  202.                 barriers separating channel interior into three
  203.                 wiring channels of 1/2, 1/4, and 1/4 of full
  204.                 channel width, removable for conversion to dual
  205.                 wiring channel of 1/2 and 1/2 width.
  206. NOTE ** Retain the following paragraph for either base
  207.         type.
  208.             c.  Cover:  Smooth finish, ivory or white color
  209.                 extruded flat profile, with continuous integral
  210.                 flanges at each edge for snap on fit to open face
  211.                 of base.
  212.  
  213.     E.  Fittings:  Supply factory-formed fittings specified in
  214.         manufacturer's product data for indicated configurations
  215.         and service requirements, and as follows:
  216.         1.  Cover clip for each vertical joint between cover unit
  217.             sections.
  218. NOTE ** Retain the following two paragraphs; edit if
  219.         project requirements differ.
  220.         2.  One wire clip for every 2 linear feet (609 mm) of
  221.             indicated base configuration.
  222.         3.  One section of replacement divider fitting for every
  223.             8 linear feet of indicated base configuration.
  224. NOTE ** Retain the following paragraph if required and
  225.         insert color requirement; available colors are
  226.         Ivory (standard), Gray, White, and Brown.
  227.         4.  Communications Fittings:  Wiremold ActivateJ
  228.             Connectivity Series modular device plates; smooth
  229.             finish.
  230. NOTE ** Retain the following paragraphs if specifying
  231.         Wiremold 5500 System.
  232.  
  233.     F.  Surface Non-Metallic Raceway:
  234.         1.  Acceptable Product:  Wiremold 5500 System.
  235.         2.  Product Description: Two-piece system of rigid
  236.             polyvinyl chloride (PVC) extrusions, 8 feet (2438 mm)
  237.             in length with nominal 0.10 inch (2.5 mm) wall
  238.             thickness, total 6-11/16 inches (139.7 mm) high by 1-
  239.             3/4 inches (44.4 mm) deep, consisting of the
  240.             following:
  241. NOTE ** Retain the following paragraph if specifying
  242.         Wiremold 5500B base.
  243.             a.  Non-Divided Base:  Smooth finish, ivory or white
  244.                 color extruded channel, with two integral
  245.                 continuous projections, equally spaced within
  246.                 channel width, to receive replacement divider
  247.                 fitting..
  248. NOTE ** Retain the following paragraph if specifying
  249.         Wiremold 5500BD base.
  250.             b.  Divided Base:  Smooth finish, ivory or white
  251.                 color extruded channel, with integral continuous
  252.                 barriers separating channel interior into three
  253.                 wiring channels, each 1/3 of full channel width,
  254.                 removable for conversion to dual or single wiring
  255.                 channel.
  256. NOTE ** Retain the following paragraph for either base
  257.         type.
  258.             c.  Cover:  Smooth finish, ivory or white color
  259.                 extruded flat profile, with continuous integral
  260.                 flanges at each edge for snap on fit to open face
  261.                 of base.
  262.  
  263.     G.  Fittings:  Supply factory-formed fittings specified in
  264.         manufacturer's product data for indicated configurations
  265.         and service requirements, and as follows:
  266.         1.  Cover clip for each vertical joint between cover unit
  267.             sections.
  268. NOTE ** Retain the following two paragraphs; edit if
  269.         project requirements differ.
  270.         2.  One wire clip for every 2 linear feet (609 mm) of
  271.             indicated base configuration.
  272.         3.  Two sections of replacement divider fitting for every
  273.             8 linear feet (2438 mm) of indicated base
  274.             configuration.
  275. NOTE ** Retain the following paragraph if required and
  276.         insert color requirement; available colors are
  277.         Ivory (standard), Gray, White, and Brown.
  278.     H.  Device Brackets and Plates:
  279.         1.  Factory-formed brackets and plates allowing
  280.             installation of indicated power, data, and
  281.             communications devices, both single-gang and two-
  282.             gang, either vertically or horizontally in raceways.
  283.         2.  Color:  ___________.
  284. NOTE ** Retain the following paragraph if required and
  285.         insert color requirement; available colors are
  286.         Ivory (standard), Gray, White, and Brown.
  287.  
  288.     I.  Cover Brackets and Face Plates:
  289.         1.  Plastic device mounting brackets and trim plates
  290.             allowing installation of indicated power, data, and
  291.             communications devices horizontally in raceways; trim
  292.             cover sized to overlap device cut-out in raceway,
  293.             concealing seams.
  294.         2.  Color:  ___________.
  295. NOTE ** Retain the following paragraph if required and
  296.         insert color requirement; available colors are
  297.         Ivory (standard), Gray, White, and Brown.
  298.  
  299.     J.  Communications Devices and Accessories:
  300.         1.  Communications devices:  Wiremold ActivateJ
  301.             Connectivity Series factory-fabricated modular
  302.             connectivity outlets, modular inserts, and other
  303.             devices for indicated configurations and service
  304.             requirements, including, but not limited to, the
  305.             following systems:
  306.             a.  UTP, including Category 5.
  307.             b.  STP; 150-ohm.
  308.             c.  Fiber Optics.
  309.             d.  Coaxial.
  310.         2.  Mounting face plates and bezels:  Color ___________.
  311.         3.  Identification accessories, including the following:
  312.             a.  Pre-printed station and port identification
  313.                 labels.
  314.             b.  Snap-in icon buttons.
  315.             c.  Write-on station identification labels.
  316. NOTE ** Retain one of the following two paragraphs.
  317.  
  318.     K.  Electrical Devices:
  319.         1.  Factory-fabricated devices for indicated
  320.             configurations and service requirements.
  321. NOTE ** Insert color requirement in the following
  322.         paragraph; available colors are Ivory (standard),
  323.         Gray, White, and Brown.
  324.         2.  Finish of sight-exposed components:  Color ________.
  325.  
  326.     L.  Electrical devices, and wiring for electrical devices,
  327.         are specified in sections of Division 16.
  328.  
  329.     M.  Fasteners:  Types specified in manufacturer's
  330.         installation instructions for project conditions.
  331.  
  332.  
  333. PART 3  EXECUTION
  334.  
  335. 3.1 EXAMINATION
  336.  
  337.     A.  Verification of Conditions:  Substrates are prepared to
  338.         receive products specified in this section.
  339.  
  340. 3.2 INSTALLATION
  341.  
  342.     A.  Install components of raceway system in accordance with
  343.         shop drawings and manufacturer's installation
  344.         instructions.
  345. NOTE ** Retain one or both of the following paragraphs, as
  346.         applicable to project.
  347.  
  348.     B.  Installation of electrical devices, and wiring of
  349.         electrical devices, is specified in a Division 16
  350.         section.
  351.  
  352.     C.  Installation of wiring for communications devices is
  353.         specified in a Division 16 section.
  354.  